Technicial Specifications
Rating Range | 30 - 3000 A |
Transfer Type | Open Transition (CG), Delayed Transition (CGD) |
Switch Type | Contactor |
Product nodes | 30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 3000A |
Rated Voltage and Frequency | 200-480VAC, 50/60 Hz |
Phase system | Single and Three (three phase only >600A) |
Number of poles | 2, 3 and 4 (3 & 4 pole only >600A) |
Neutral configuration | Optional Solid or Switched neutral |
Product type | Open transition (I-II), Delayed Transition (I-O-II) |
Advantages and Features
Product Features
- Voltage and frequency sensing of both sources and load
- USB port to upload/download settings
- Available Bluetooth connection and enhanced communication capabilities
- Password protection LCD HMI
- Integrated help button and menu
- Automatic Configuration Function
Control Panel
- TruOne L3 - CG LCD HMI to set electrical system parameters with file upload via USB or Bluetooth connection.
Functions
- Provision of transfer & re-transfer control signals
- Provision of engine/generator start and shutdown signals
- Permit user programming of set points
- Display real time and historical information
- Permit system testing
- Store all parameters in nonvolatile memory
Standards
- UL 1008, NFPA 70, 99, 101 and 110
- NEMA ICS 10
- cUL
Standard Equipment
-
Control
- LCD + keys
- Voltage and frequency settings: Pick up and Drop out
- Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF, Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead
- Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence
-
Additional Features
- LED indications for ATS, S1 and S2 status
- Open transition - Standard digital inputs/outputs (1/1)
- Delayed transition - Standard digital inputs/outputs (2/1)
- Programmable digital inputs/outputs
- Auto config (voltage, frequency, phase system)
- Source priority (Source 1/2, No priority)
- Manual re-transfer
- In-phase monitor (synchro check)
- Genset exercising: on-load, off-load
- Load shedding
- Real time clock
- Event log
Optional Equipment
-
Accessories
- Auxiliary contacts for position indication
- Additional digital input/output contacts (adding up to 6 each)
- 12-24 VDC aux supply module for controller
- Communication modules
-
Connectivity Capability
- Modbus RTU (RS-485)
- Modbus/TCP
- Profibus DP
- ProfiNet Yes
- DeviceNet
- Ethernet IP