Input Control Voltage |
—
65 to 145 Vac 50/60 hZ
|
Voltage Measurements of Utility |
—
Source 1 VAB Source 2 VAB<br>Source 1 VAC Source 2 VBC<br>Source 1 VCA Source 2 VCA
|
Voltage Measurement Range |
—
0 to 790 VAC rms (50/60 Hz)
|
Voltage Measurement Accuracy |
—
+/-2% of nominal input voltage
|
Frequency Measurements Of |
—
Source 1 and Source 2
|
Frequency Measurement Range |
—
40 Hz to 70 Hz
|
Frequency Measurement Accuracy |
—
+/- 0.1 Hz
|
Undervoltage Dropout |
—
50% to 90% of nominal voltage
|
Undervoltage Pickup |
—
(Dropout +2%) to 99% of the nominal system voltage
|
Underfrequency Dropout Range |
—
90 to 97% of the nominal system frequency
|
Underfrequency Pickup Range |
—
(Dropout +1 Hz) to 99% of the nominal system frequency
|
Overfrequency Dropout Range |
—
103 to 110% of the nominal system frequency
|
Overfrequency Pickup Range |
—
101% to (dropout - 1 Hz) of the nominal system frequency
|
Operating Temperature Range |
—
-20 to 70 degree C (-4 to +158 degree F)
|
Storage Temperature Range |
—
-30 to 85 degree C (-22 to +185 degree F)
|
Operating Humidity |
—
0 to 95% relative humidity (noncondensing)
|
Operating Environment |
—
Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbons
|
Generator Start Relay |
—
5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum load
|
K1, K2 Relays |
—
<br>10A, 1-3 hp @ 250 Vac</br><br>10A@30 Vdc</br>
|
Applicable Testing |
—
UL-recognized component<br>Meets intent of UL 991 & UL 1008<br>Meets IEC 1000-4-2, 1000-4-3, 1000-4-4
|
Applicable Testing Continued |
—
1000-4-5, 1000-4-6, 1000-4-11<br>CISPR 11, Class A<br>FCC Part 15, Class A<br>CSS 22.2-178
|
Enclosure Compatibility |
—
NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-300+ faceplate
|